Low-frequency transformers for UPS, inverter and energy-storage systems: crest-factor loads, battery recharge windings, isolation and the thermal margin that keeps a UPS alive during overload.
Why UPS designs still use a low-frequency transformer
A line-interactive or online UPS with a mains-frequency transformer isolates the DC bus from the load, blocks DC injection, and gives the inverter a clean, low-impedance source to switch against. It also provides the voltage translation the battery stack cannot, and can carry a second winding for the charger. High-frequency designs save weight; transformer-based designs survive overloads and inrush far better — which is what buyers actually notice.
What the transformer has to survive
- Non-linear load. Switch-mode loads draw current in peaks, not sine waves. Crest factors of 2.5–3 are normal; specify the transformer for that, not for the VA number alone.
- Overload. A UPS is expected to carry 125–150% for a minute and 200% for seconds. The transformer's thermal design decides whether that is possible.
- Inverter switching. PWM edges stress winding insulation; low leakage inductance keeps the output waveform clean.
- Charger windings. Extra secondary for battery recharge, with its own current rating and isolation.
How to specify it
Send the UPS topology (online, line-interactive, delta conversion), DC bus voltage, output voltage and phase configuration, kVA rating, overload profile, crest factor of the target loads, and whether a charger winding is needed. For solar and storage inverters, send the DC input window and the grid voltage — we build step-up and isolation transformers for both. Typical builds sit between 600 VA and 1000 kVA, Class F or H, AN or AF cooled.
Related pages
- Toroidal transformers for UPS & inverters
- EI transformers for UPS & inverters
- Toroidal transformers for solar inverters
Talk to an engineer
Describe the symptom you are chasing — the noise, the trip, the heat, the space you have — and we will come back with a transformer proposal rather than a catalogue part. Send drawings or a target price and we normally reply within 24 hours on working days.
Contact our sales engineers → | Request a formal quotation →
Why NRE
NRE has manufactured transformers since 1994, with plants in Guangdong and Hubei covering nearly 100 mu and 62,700 m². Annual capacity is about 8 million toroidal transformers, 30 million EI transformers and 200,000 special transformers, with close to 150 engineers on the design and process side. We build to print, to specification, or from a problem description.