Why a variable-frequency drive overheats its capacitors, trips its breaker or pollutes the supply — and how line reactors, load reactors and K-factor transformers are sized to fix it.
The symptom
A drive that runs fine at light load but trips or overheats at 70–80% load. DC-bus capacitors running hot. Other equipment on the same supply behaving oddly. A supply transformer that runs hotter than its kVA suggests. These are the fingerprints of harmonic current drawn by a six-pulse rectifier front end.
What a six-pulse drive actually draws
Current is drawn in short pulses near the peak of the voltage wave, so the current waveform is rich in 5th, 7th, 11th and 13th harmonics. Total harmonic distortion of current can reach 80–120% before any mitigation. Two things follow: the drive sees a distorted DC bus, and every upstream component — transformer, cable, breaker — carries harmonics it was not sized for.
The three fixes, in cost order
- Line (input) reactor — typically 3–5% impedance, fitted between supply and drive. Reduces current THD, smooths the DC bus, cuts capacitor heating. Cheapest effective step, and the one most often missing.
- Load (output) reactor — between drive and motor, for long cable runs or older motors. Limits dv/dt and common-mode current, protects motor insulation.
- K-factor transformer or harmonic filter — when several drives share a supply, or the supply transformer must be derated. K-13 / K-20 designs carry harmonic loading without overheating; passive filters trap the 5th and 7th.
Sizing rules we use
Reactor current rating is chosen for the motor's full-load current, with margin for overload; impedance is chosen by how much THD reduction the site needs — 3% is the common default, 4–5% for weaker supplies. For a bank of drives on one skid, the question is whether to fit one reactor per drive or one at the common feed: per-drive is the correct answer when each drive is independently rated, a shared reactor only protects the shared bus. Send the single-line diagram and we will mark it up.
Related pages
- Reactors for VFD and harmonic filtering
- Guide: line reactor vs load reactor for VFDs
- Guide: K-factor transformers for non-linear loads
Talk to an engineer
Describe the symptom you are chasing — the noise, the trip, the heat, the space you have — and we will come back with a transformer proposal rather than a catalogue part. Send drawings or a target price and we normally reply within 24 hours on working days.
Contact our sales engineers → | Request a formal quotation →
Why NRE
NRE has manufactured transformers since 1994, with plants in Guangdong and Hubei covering nearly 100 mu and 62,700 m². Annual capacity is about 8 million toroidal transformers, 30 million EI transformers and 200,000 special transformers, with close to 150 engineers on the design and process side. We build to print, to specification, or from a problem description.